- PT1000 to 0-10 V or 4-20 mA
- -50…+250°C
- top hat rail mounting
- protection type IP20
The temperature transducer for DIN rail mounting measures the temperature by the Pt1000-Sensor-Input and transforms the measured value to a linear output signal 0-10 V or 4-20 mA. The DIN rail transmitter is operated as a 2-wire Connection. The scaling is set at the factory at the customer’s request. The DIN rail transducer is in control cabinets or distribution boxes quickly and securely mounted by snapping onto the DIN rail.
Scales: | -50…0°C, -50…+50°C, -50…+150°C, -30…+20°C, -30…+70°C, -20…+50°C, -20…+80°C, -20…+120°C, -20…+150°C, -10…+15°C, 0…+50°C, 0…+100°C, 0…+150°C, 0…+200°C, 0…+250°C, +10…+35°C |
Accuracy: | ±0,2 K + max. ±1,5% Span |
Sensor: | Pt100 DIN EN 60751 Kl. B (not in scope of delivery) |
Supply voltage analog 0-10 V: | 24 V AC/DC (±5%) |
Supply voltage analog 4-20 mA: | 15…36 V DC, depends on liability (Ubmin = 15 V + Rload*0,02A) |
Current consumption at 0-10 V: | typ. 10 mA |
Current consumption at 4-20 mA: | max. 20 mA / output |
Analogue output 0-10 V: | 3-wire connection, min. load resistance 100 kOhm |
Analogue output 4-20 mA: | 2-wire connection (transmitter), max. RLoad(Ohm) = (+Ub – 15 V) / 0,02 A |
Electrical connection: | screw terminals max. 2,5 mm² |
Protection type: | IP20 |
Protection class: | III |
Working range r.H.: | 0…98% r.H. in contaminant-free, non-condensing air |
Working temperature: | Electronic: -20…+70°C |
Storage temperature: | -20…+70°C |
Installation: | snap-on mounting onto cap rail |
Approvals: | CE, EAC, RoHS |