- -50…+150°C
- output 0-10 V, 4-20 mA
- protection type IP65
- Pmax. 40 bar
- thread G1/2 inch
The screwable transducer with connection head form B, neck tube and interchangeable measuring insert registers the temperature at a maximum pressure of 40 bar in gaseous and liquid media and converts this measured value into a linear output signal 0-10 V respectively 4-20 mA. Using the stainless steel immersion sleeve, with G1/2 inch thread, the temperature transducer is screwed directly into the container or the pipeline. With the neck tube an better heat dissipation is achieved.
Measurement range temp.: | -30…+180°C |
Scales: | -50…0°C, -50…+50°C, -50…+150°C, -30…+20°C, -30…+70°C, -20…+50°C, -20…+80°C, -20…+120°C, -20…+150°C, -10…+15°C, 0…+50°C, 0…+100°C, 0…+150°C, 0…+200°C, 0…+250°C, +10…+35°C |
Accuracy: | ±0,2 K + max. ±1,5% Span |
Supply voltage analog 0-10 V: | 24 V AC/DC (±5%) |
Supply voltage analog 4-20 mA: | 15…36 V DC, depends on liability (Ubmin = 15 V + Rload*0,02A) |
Current consumption at 0-10 V: | typ. 10 mA |
Current consumption at 4-20 mA: | max. 20 mA / output |
Analogue output 0-10 V: | 3-wire connection, min. load resistance 100 kOhm |
Analogue output 4-20 mA: | 2-wire connection (transmitter), max. RLoad(Ohm) = (+Ub – 15 V) / 0,02 A |
Electrical connection: | push-in terminals, max. 1,5 mm² |
Material: | Protection sleeve: stainless steel VA 1.4571 |
Cable gland: | M20x1,5 cable gland with strain relief |
Housing: | terminal head form B , aluminium, colour grey |
Dimensions: | Neck tube length: 80 mm |
Protection type: | IP65 |
Protection class: | III |
Working range r.H.: | 0…98% r.H. in contaminant-free, non-condensing air |
Working temperature: | Probe: -30…+180°C, Electronic: -20…+70°C |
Storage temperature: | -20…+70°C |
Installation: | screw-in thread G1/2 inch |
Approvals: | CE, EAC, RoHS |