- -30…+150°C
- Modbus RTU, relay
- DIP-switch-technology
- optional with LCD-Display
- protection type IP65
- incl. mounting flange
- hinge lock technology
The FS1021 duct transducer registers the temperature in gaseous media and converts this measured value into a digital output signal.Using the mounting flange, included in the scope of delivery, the temperature transducer is fastened, for example, directly to the duct, container etc. and can be quickly and easily be replaced during service.As special equipment a potential-free alternating contact and/or a backlit display are available The contents of the display can be rotated in steps of 90° by using a command.As special functions a series of defined measured values from other bus-participants (also cross-manufacturers) can be shown in the display. To display measured values from other bus-participants these are entered into the corresponding register by the bus-Master. The optional alternating contact can be configurated for measured values from other bus-participants.The configuration of address, transmission mode/speed, terminating resistor and master/slave function of the bus-devices can easily be done using the innovative DIP switch technology. Thus devices can quickly and easily integrated into the system and later parameterised via the master.The bus-devices can even be reset to the works settings during operation of the master. Thus the basic functionality of the device is recreated in a matter of seconds. This can be necessary in the event of incorrect parameterisations of, e.g. offset, switching threshold, display modes etc..By means of the FS master/slave topology autarkic nodes without additional SPS master can be installed within the device series. Hereby a bus-device assumes the master function in the node. This requests the measured values from other bus-participants, automatically enters these into the corresponding register and shows them in the internal display. Furthermore the master can evaluate and operate additional actuators in the device series (analogue in- and outputs, relay station).
Measurement range temp.: | -30…+150°C |
Accuracy: | ±0,2 K + max. ±1% mv (-30?+100°C), else ±0,3 K + max. ±1,5% mv |
Supply voltage: | 24 V DC (±5%) |
Current consumption: | max. 20 mA + 30 mA (option display) + 20 mA (option relay) |
Alarm output: | 1 x potential-free change-over contact, 48 V, 1 A |
Digital output: | Modbus RTU |
Switching Hysteresis Relay: | can be entered in the register |
Offset: | can be entered in the register |
Electrical connection: | push-in terminal, no tools required, time-saving |
Display: | optional LCD display with backlight on/off/auto |
Material: | Protection sleeve: stainless steel VA 1.4571 |
Cable gland: | PG11 high-strength cable gland with strain relief |
Housing: | Polycarbonate PC UL 94 V0 with hinge locks, color signal white similar to RAL 9003 |
Dimensions: | Housing: L 89 x W 80 x H 47 mm, Protection sleeve: Ø 6 mm |
Protection type: | IP65 |
Protection class: | III |
Working range r.H.: | 0…98% r.H. in contaminant-free, non-condensing air |
Working temperature: | Probe: -30…+150°C, Electronic: -20…+70°C |
Storage temperature: | -20…+70°C |
Installation: | mounting flange (in scope of delivery) |
Approvals: | CE, EAC, RoHS |