  • -30…+150°C
  • 16 measuring ranges per device
  • output 0-10 V, 4-20 mA
  • DIP-switch-technology
  • optional with LCD-Display
  • protection type IP65
  • incl. mounting flange
  • hinge lock technology

  • The KM/E cable transducer registers the temperature in gaseous media and converts this measured value into a linear output signal 0-10 V respectively 4-20 mA.As an option the temperature transducer has two potential-free changeover contacts and a backlit display. The display content can be rotated in 90° steps using a menu and the measured value, the switching threshold set, the state of the respective relay, the MIN/MAX measured values for the selected intervals(1 h / 6 h / 12 h / 24 h) etc. can be read out.On the display version the user can, via the menu, specify an individual temperature range.Using the installation flange, included in the scope of delivery, the temperature transducer is fastened, for example, directly to the duct, container etc. and can be quickly and easily be replaced during service.

    Measurement range temp.: -30…+150°C
    Measurement range configuration: 1 freely programmable measuring range via the menu input in the display (span min. 25K)
    Scales: -50…0°C, -50…+50°C, -50…+150°C, -30…+20°C, -30…+70°C, -20…+50°C, -20…+80°C, -20…+120°C, -20…+150°C, -10…+15°C, 0…+50°C, 0…+100°C, 0…+150°C, 0…+200°C, 0…+250°C, +10…+35°C
    Accuracy: ±0,2 K + max. ±1,5% Span
    Supply voltage analog 0-10 V: 24 V AC/DC (±5%)
    Supply voltage analog 4-20 mA: 15…36 V DC, depends on liability (Ubmin = 15 V + Rload*0,02A)
    Current consumption at 0-10 V: typ. 10 mA, 30 mA peak current consumption for 50 ms at switching moment at option relay
    Current consumption at 4-20 mA: max. 20 mA / output, 40 mA peak current consumption for 50 ms at switching moment at option relay
    Analogue output 0-10 V: 3-wire connection, min. load resistance 100 kOhm
    Analogue output 4-20 mA: 2-wire connection (transmitter), max. RLoad(Ohm) = (+Ub – 15 V) / 0,02 A
    Alarm output: 2 x potential-free change-over contact, 48 V, 1 A
    Switching Hysteresis Relay: Temperature: 2K (without display), 0,5…5K adjustable (with display)
    Electrical connection: screw terminals max. 1,5 mm²
    Display: optional LCD display with backlight on/off/auto
    Material: Protection sleeve: stainless steel VA 1.4571
    Cable gland: PG11 high-strength cable gland with strain relief
    Housing: Polycarbonate PC UL 94 V0 with hinge locks, color signal white similar to RAL 9003
    Dimensions: Housing: L 89 x W 80 x H 47 mm, Protection sleeve: Ø 6 mm
    Protection type: IP65
    Protection class: III
    Working range r.H.: 0…98% r.H. in contaminant-free, non-condensing air
    Working temperature: Probe: -30…+150°C, Electronic: -20…+70°C
    Storage temperature: -20…+70°C
    Installation: mounting flange (in scope of delivery)