- Rotary actuator without spring return actuator
- 120…230 VAC/DC, 2/3 point
- Torque 10 Nm
- Running time 150 s/90°
- Connection with 1m cable
- Feedback signal: Auxiliary switch
- Shaft coupling: O 8-20 mm, square 8-15 mm
- Assembly with mounting strip + screws
Rotary actuator for adjusting dampers in HVAC installationsRunning time: 150 s / 90°Torque: 10 NmNominal voltage: 230 VAC/DCControl: 2-/3-pointAuxiliary switch: 1x freely adjustableDamper size: up to approx. 2 m²Shaft coupling: clamp square 8-15 mm / round 8-20 mm
Electrical data: | |
Nominal voltage: | 230 VAC/DC, 50/60 Hz |
Nominal voltage range: | 85…265 VAC/DC |
Power consumption motor (motion): | 2,0 W |
Power consumption standby (end position): | 1,0 W |
Wire sizing: | 4,5 VA |
Control: | 2-/3-point |
Feedback signal: | – |
Connection motor: | cable 1000 mm, 3 x 0,75 mm² (halogen free) |
Auxiliary switch: | 1x SPDT (Ag) |
Functional data: | |
Contact load: | 5 (2,5) A, 250 VAC |
Switching point: | 0°…95° |
Synchronised speed: | ±5% |
Connection feedback potentiometer: | – |
Connection auxiliary switch: | cable 1000 mm, 3 x 0,75 mm² (halogen free) |
Connection GUAC: | – |
Sound power level: | < 35 dB(A) |
Torque: | 10 Nm |
Safety: | |
Damper size: | up to approx. 2 m² |
Protection class: | II (double insulation) |
Degree of protection: | IP 54 (cable downwards) |
Direction of rotation: | selected by switch |
EMC: | CE (2014/30/EU) |
Manual override: | gearing latch disengaged with pushbutton, self-resetting |
LVD: | CE (2014/35/EU) |
Angle of rotation: | 0°…max. 95° can be limited with adjustable mechanical end stops |
RoHS: | CE (2011/65/EU – 2015/863/EU – 2017/2102/EU) |
Running time: | 150 s / 90° |
Mode of operation: | Typ 1 (EN 60730-1) |
Rated impulse voltage: | 4 kV (EN 60730-1) |
Shaft coupling: | clamp ◊ 8-15 mm / Ø 8-20 mm |
Control pollution degree: | 3 (EN 60730-1) |
Position indication: | mechanical with pointer |
Ambient temperature normal operation: | -30°C…+50°C |
Service life: | > 60 000 cycles (0°…95°…0°) |
Storage temperature: | -30°C…+80°C |
Ambient humidity: | 5…95% r.H., non condensing (EN 60730-1) |
Maintenance: | maintenance free |
Dimensions / Weight: | |
Dimensions: | 115 x 65 x 61 mm |
Weight: | 450 g |