- -5000…+5000 Pa, 0-200.000 m³/h
- 8 measurement ranges per version
- 0-10 V, 4-20 mA,relay
- output attenuation 0 sec. / 1 sec. / 5 sec. / 10 sec. by DIP-switch selectable
- hinge lock technology
The pressure transmitter detects the overpressure, underpressure or differential pressure (P) between the two pressure inputs and converts the measured value into a linear output signal 0-10 V or 4-20 mA. 8 different scalings and the output damping of the pressure transmitter (0 sec / 1 sec / 5 sec / 10 sec) can be set on the device.Alternatively, the measuring device can be operated as a volume flow measuring device. It calculates the volume flow (Q) using the system-specific K factor (k) and outputs the calculated value as a linear output signal 0-10 V or 4-20 mA. The K-factor, the desired scaling for the volume flow output signal 0-10 V or 4-20 mA, the density of the medium and the desired volume unit (l or m³ per s / min / h) can be conveniently set via the display menu.The content of the backlit display can be rotated in 90 ° steps via the menu and the actual value, the set switching threshold, the relay status, the MIN / MAX measured values of the selected interval (1 h / 6 h / 12 h / 24 h) etc. can be read. For manual calibration of the zero point on site, the pressure transmitter carries out a zero point adjustment at the push of a button. If necessary, the pressure transmitter can be fine-calibrated on site using a SPAN controller.
Pressure type: | positive, negative or differential pressure |
Medium: | air, non-aggressive, non-flammable, non-condensing gases |
Measurement range pressure: | V1: 0…+/-500 Pa, V2: 0…+/-5000 Pa, V3: 0…+/-100 Pa |
Measurement range volume flow (calculated): | V1: 0-65.000 m³/h, V2: 0-200.000 m³/h, V3: 0-30.000 m³/h |
Scales: | V1: 0…+/-100, 0…+/-200 Pa, 0…+/-300 Pa, 0…+/-500 Pa; V2: 0…+/-1000, 0…+/-2000 Pa, 0…+/-3000 Pa, 0…+/-5000 Pa; V3: 0…+/-25, 0…+/-50 Pa, 0…+/-75 Pa, 0…+/-100 Pa |
Accuracy: | ±3,0% FS (at 20°C) |
Temperature dependency: | ±2,5% FS / 10 K |
Linearity inaccuracy: | ±1,0% final value |
Long term stability: | ±1% FS/year |
Zero-point adjustment: | max. +2% final value |
Pressure resistance: | 5-times of measurement range |
Sensor protection: | mounted inside housing |
Supply voltage analog 0-10 V: | 24 V AC/DC (±5%) |
Supply voltage analog 4-20 mA: | 15…36 V DC (Ubmin = 15 V + RLoad*0,02A) |
Current consumption at 0-10 V: | typ. 15 mA, 30 mA peak current consumption for 50 ms at switching moment at option relay |
Current consumption at 4-20 mA: | max. 20 mA / output, 40 mA peak current consumption for 50 ms at switching moment at option relay |
Analogue output 0-10 V: | 3-wire connection, min. load resistance 100 kOhm |
Analogue output 4-20 mA: | 2-wire connection (transmitter), max. RLoad(Ohm) = (+Ub – 15 V) / 0,02 A |
Alarm output: | 1 x potential-free change-over contact, 48 V, 1 A |
Switching Hysteresis Relay: | 2% of the selected scaling (without display), 0,5…5% of the selected scaling adjustable (with display) |
Offset: | ±5% from the selected scale by 270° potentiometer |
Electrical connection: | screw terminals max. 1,5 mm² |
Display: | optional LCD display with backlight on/off/auto |
Output attentuation: | 0 s / 1 s / 5 s / 10 s selectable by DIP switch |
Running-in time: | < 30 min at initial operation because of tempering |
Reaction rate: | < 1 s, at 5% alteration relating to final value |
Cable gland: | PG11 high-strength cable gland with strain relief |
Housing: | Polycarbonate PC UL 94 V0 with hinge locks, color signal white similar to RAL 9003 |
Dimensions: | Housing: L 89 x W 80 x H 47 mm |
Protection type: | IP65, IP20 if pressure connection port is open |
Protection class: | III |
Working range r.H.: | 0…98% r.H. in contaminant-free, non-condensing air |
Working temperature: | 0…+50°C |
Manual zero-point adjustment: | The zero point adjustment is started by pressing the button on the circuit board (push 10 s until LED stops flashing or by the display version the countdown 10-0 is completed). Before, a continuous operation of at least 1 hour must be sure, the offset must be in the middle position and the pressure inputs P+ and P- must be an obvious offense to the environment. The successful calibration will be signalized by 5 sec durable lightning of the LED. |
Storage temperature: | 0…+50°C |
Installation: | Housing: screw fastening, Pressure connection: 2 plastic duct connecting nipple with fastening screws and 2 m PVC tube Ø 6 mm (in scope of delivery) |
Approvals: | CE, EAC, RoHS |