  • % r.H.
  • output 0-10 V, 4-20 mA, changer
  • heating function for condensation protection
  • accuracy ±3% r.H.
  • hinge lock technology

  • The humidity transducer with contact block registers the relative humidity at the contact point contact prism/tube and converts this measured value into a line-ar output signal 0-10 V respectively 4-20 mA.As an option the device has a potential-free changeover contact and a backlit display.The display content can be rotated in 90° steps using a menu and the measured value, the switching threshold set, the state of the respective relay, the MIN/MAX measured values for the selected intervals (1 h / 6 h / 12 h / 24 h) etc. can be read out. The value measured in addition to the temperature can be selected from the 4 parameters % r.h., g/m³, g/kg, dp can easily be selected per DIP switch.In addition the humidity measuring device has a heating function to protect the sensor at high humidity 95…99% r.h.. If the relative humidity exceeds the threshold value set ex-works for a certain period of time the heating function is activated. The sensor is heated for a limited time and thus dried and protected against condensation. During the heating and the subsequent temperature balancing phase the output signal is kept stable at the last measured value before the heating function was triggered.The humidity sensor is very well protected against contamination by a sintered filter and can, if required, be finely calibrated in situ using an offset controller.

    Measurement range r.H.: 0-100% r.H.
    Accuracy humidity: ±3% r.H. (30-70% r.H., else ±5% r.H., at 20°C)
    Temperature dependency: ±0,02% r.H. / K (voltage output), ±0,04% r.H. / K (current version); ±0,05°C / 10 K (voltage version), ±0,07°C / 10 K (current output)
    Long term stability: ±1%/year
    Sensor: capacitive humidity sensor
    Sensor protection: sinter filter, sensor mounted inside the contact block
    Supply voltage analog 0-10 V: 24 V AC/DC (±5%)
    Supply voltage analog 4-20 mA: 15…36 V DC (Ubmin = 15 V + RLoad*0,02A)
    Current consumption at 0-10 V: typ. 10 mA, 30 mA peak current consumption for 50 ms at switching moment at option relay
    Current consumption at 4-20 mA: max. 20 mA / output, 40 mA peak current consumption for 50 ms at switching moment at option relay
    Analogue output 0-10 V: 3-wire connection, load current < 0,1 mA
    Analogue output 4-20 mA: 2-wire connection (transmitter), max. RLoad(Ohm) = (+Ub – 15 V) / 0,02 A
    Alarm output: 1 x potential-free change-over contact, 48 V, 1 A
    Switching Hysteresis Relay: 2% of the selected scaling (without display), 0,5…5% of the selected scaling adjustable (with display)
    Electrical connection: screw terminals max. 1,5 mm²
    Display: optional LCD display with backlight (on/off/auto at 0-10 V version, at 4-20 mA version via DBL terminal)
    Material: Contacting block: aluminium
    Flow rate: < 2 m/s
    Cable gland: PG11 high-strength cable gland with strain relief
    Housing: Polycarbonate PC UL 94 V0 with hinge locks, color signal white similar to RAL 9003
    Dimensions: Housing: L 89 x W 80 x H 47 mm, Contacting block: L 25 x W 54 x H 15 mm,
    Protection type: Housing/electronic: IP65, Sensor: IP30
    Protection class: III
    Working range r.H.: 0…98% r.H. in contaminant-free, non-condensing air
    Working temperature: Probe: -20…+80°C, Electronic: 0…+50°C
    Storage temperature: 0…+50°C
    Installation: clamping band, band width 9 mm, chucking capacity 50-110 mm, galvanized steel (in scope of delivery)