- % r.H., g/m³, g/kg, DP °C
- -30…+70°C, -20…+80°C, 0…+50°C, 0…+100°C
- output 0-10 V, 4-20 mA, changer
- heating function for condensation protection
- accuracy ±3% r.H.
- hinge lock technology
The humidity and temperature transducer with contact block registers the temperature and, optionally, the relative humidity, absolute humidity, the mixing ratio or the dew point of the air in the environment and converts this measured value into a linear output signal 0-10 V respectively 4-20 mA.As an option the device has a potential-free changeover contact and a backlit display.The changeover contact can be defined for one of the two measured values.The display content can be rotated in 90° steps using a menu and the measured value, the switching threshold set, the state of the respective relay, the MIN/MAX measured values for the selected intervals (1 h / 6 h / 12 h / 24 h) etc. can be read out. The value measured in addition to the temperature can be selected from the 4 parameters % r.h., g/m³, g/kg, dp can easily be selected per DIP switch.In addition the humidity measuring device has a heating function to protect the sensor at high humidity 95…99% r.h.. If the relative humidity exceeds the threshold value set ex-works for a certain period of time the heating function is activated. The sensor is heated for a limited time and thus dried and protected against condensation. During the heating and the subsequent temperature balancing phase the output signal is kept stable at the last measured value before the heating function was triggered.The humidity and temperature sensor is very well protected against contamination by a sintered filter and can, if required, be finely calibrated in situ using an offset controller.
Measurement range temp.: | -20…+80°C |
Measurement range abs. humidity: | 0-50 g/m³, 0-80 g/m³ (calculated) selectable by DIP switch |
Measurement range air fuel ratio: | 0-50 g/kg, 0-80 g/kg (calculated) selectable by DIP switch |
Measurement range r.H.: | 0-100% r.H. |
Measurement range dew point: | -20…+50°C DP, -20…+80°C DP, 0…+50°C DP (calculated) selectable by DIP switch |
Accuracy humidity: | ±3% r.H. (30-70% r.H., else ±5% r.H., at 20°C) |
Accuracy temperature: | ±0,5 K |
Scales: | -30…+70°C, -20…+80°C, 0…+50°C, 0…+100°C selectable by DIP switch |
Temperature dependency: | ±0,02% r.H. / K (voltage output), ±0,04% r.H. / K (current version); ±0,05°C / 10 K (voltage version), ±0,07°C / 10 K (current output) |
Long term stability: | ±1%/year |
Sensor: | Combined electronic humidity and temperature sensor |
Sensor protection: | sinter filter, sensor mounted inside the contact block |
Supply voltage analog 0-10 V: | 24 V AC/DC (±5%) |
Supply voltage analog 4-20 mA: | 15…36 V DC (Ubmin = 15 V + RLoad*0,02A) |
Current consumption at 0-10 V: | typ. 10 mA, 30 mA peak current consumption for 50 ms at switching moment at option relay |
Current consumption at 4-20 mA: | max. 20 mA / output, 40 mA peak current consumption for 50 ms at switching moment at option relay |
Analogue output 0-10 V: | 3-wire connection, load current < 0,1 mA |
Analogue output 4-20 mA: | 2-wire connection (transmitter), max. RLoad(Ohm) = (+Ub – 15 V) / 0,02 A |
Alarm output: | 1 x potential-free change-over contact, 48 V, 1 A |
Switching Hysteresis Relay: | 2% of the selected scaling (without display), 0,5…5% of the selected scaling adjustable (with display) |
Electrical connection: | screw terminals max. 1,5 mm² |
Display: | optional LCD display with backlight (on/off/auto at 0-10 V version, at 4-20 mA version via DBL terminal) |
Material: | Contacting block: aluminium |
Flow rate: | < 2 m/s |
Cable gland: | PG11 high-strength cable gland with strain relief |
Housing: | Polycarbonate PC UL 94 V0 with hinge locks, color signal white similar to RAL 9003 |
Dimensions: | Housing: L 89 x W 80 x H 47 mm, Contacting block: L 25 x W 54 x H 15 mm, |
Protection type: | Housing/electronic: IP65, Sensor: IP30 |
Protection class: | III |
Working range r.H.: | 0…98% r.H. in contaminant-free, non-condensing air |
Working temperature: | Probe: -20…+80°C, Electronic: 0…+50°C |
Storage temperature: | -20…+50°C |
Installation: | clamping band, band width 9 mm, chucking capacity 50-110 mm, galvanized steel (in scope of delivery) |
Approvals: | CE, RoHS |