- % r.H., g/m³, g/kg, DP °C
- max. 10 bar
- output 0-10 V, 4-20 mA, changer
- heating function for condensation protection
- LCD display, relay
- hinge lock technology
The humidity transmitter FS3135 detects the temperature and relative humidity in compressed air lines up to max. 10 bar and converts the measured values into an active 0-10 V or 4-20 mA output signal. The additional measured value for the temperature can be simply selected via the DIP switch from the 4 measured values% r.h., g / m³, g / kg, TP.As an option, a potential-free changeover contact and / or a backlit LCD display are available.The changeover contact can be defined for one or both measured values.The content of the backlit display can be rotated by the menu in 90 ° increments. The actual value, the set switching threshold, the relay status, the MIN / MAX measured values of the selected interval, etc. can be read off.The switching threshold, hysteresis, offset value, etc. can be set directly on the device.In addition, the moisture meter has a heating function for sensor protection in the high humidity range of 95 … 99% rh. If the relative humidity exceeds the threshold value set ex-works for a certain period of time the heating function is activated. The sensor is heated for a limited time, thus dried or protected against condensation. During the heating and subsequent temperature compensation phase, the output signal is kept stable to the last measured value before activation of the protective function.The sensor technology is optimally protected against contamination by a screwable sintered filter.
Measurement range temp.: | -20…+80°C |
Measurement range abs. humidity: | 0-50 g/m³, 0-80 g/m³ (calculated) selectable by DIP switch |
Measurement range air fuel ratio: | 0-50 g/kg, 0-80 g/kg (calculated) selectable by DIP switch |
Measurement range r.H.: | 0-100% r.H. |
Measurement range dew point: | -20…+50°C DP, -20…+80°C DP, 0…+50°C DP (calculated) selectable by DIP switch |
Accuracy humidity: | ±3% r.H. (30-70% r.H., else ±5% r.H., at 20°C) |
Accuracy temperature: | ±0,5 K |
Scales: | -20…+80°C, -0…+50°C, -50…+50°C, 0…+100°C selectable by DIP switch |
Temperature dependency: | ±0,02% r.H. / K (voltage output), ±0,04% r.H. / K (current version); ±0,05°C / 10 K (voltage version), ±0,07°C / 10 K (current output) |
Long term stability: | ±1%/year |
Pressure resistance: | max. 10 bar |
Sensor: | Combined electronic humidity and temperature sensor |
Response time (t90): | < 90 s |
Sensor protection: | screwable stainless steel sinter filter, condensation protection by heating function in the range of 95…99% r.H. |
Supply voltage analog 0-10 V: | 24 V AC/DC (±5%) |
Supply voltage analog 4-20 mA: | 15…36 V DC (Ubmin = 15 V + RLoad*0,02A) |
Current consumption at 0-10 V: | typ. 10 mA, 30 mA peak current consumption for 50 ms at switching moment at option relay |
Current consumption at 4-20 mA: | max. 20 mA / output, 40 mA peak current consumption for 50 ms at switching moment at option relay |
Analogue output 0-10 V: | 3-wire connection, load current < 0,1 mA |
Analogue output 4-20 mA: | 2-wire connection (transmitter), max. RLoad(Ohm) = (+Ub – 15 V) / 0,02 A |
Alarm output: | 1 x potential-free change-over contact, 48 V, 1 A |
Switching Hysteresis Relay: | 2% of the selected scaling (without display), 0,5…5% of the selected scaling adjustable (with display) |
Electrical connection: | screw terminals max. 1,5 mm² |
Display: | optional LCD display with backlight on/off/auto |
Running-in time: | < 5 min (U-Version), < 10 min (I-Version) |
Material: | Protection tube: stainless steel V2A |
Flow rate: | < 2 m/s |
Cable gland: | PG11 high-strength cable gland with strain relief |
Housing: | Polycarbonate PC UL 94 V0 with hinge locks, color signal white similar to RAL 9003 |
Dimensions: | Housing: L 89 x W 80 x H 47 mm, Protection tube: Ø 20 x 115 mm, SW 24, immersion depth 25 mm, G1/2 inch thread |
Protection type: | Housing/electronic: IP65, Sensor: IP30 |
Protection class: | III |
Working range r.H.: | 0…98% r.H. in contaminant-free, non-condensing air |
Working temperature: | -20…+50°C |
Storage temperature: | -20…+50°C |
Installation: | screw-in thread |
Approvals: | CE, EAC, RoHS |