- % r.h., g/m³, g/kg, °C, DP °C, WB °C
- continuous heated sensor
- high humidity range up to 99%
- slight pollutant concentration
- LCD display, relay
- hinge lock technology
The humidity transmitter FS3130 detects the temperature and relative humidity in air ventilation ducts and converts the measured values into an active 0-10 V or 4-20 mA output signal. In addition, a further thermodynamic indicator calculated from the measured values can be transmitted at the third output, e.g. mixing ratio, absolute humidity, dew point temperature or wet bulb temperature are output. The third output signal can be selected via DIP switch.The moisture meter has a continuous heating function and is specially designed for use in the high humidity range of 95 … 99% relative humidity. Thereby, a much faster reaction rate with changes in relative humidity, even in the range > 95% r.h. is reached. The combined digital humidity and temperature sensor is heated approx. 3K above ambient temperature. From the measured rel. humidity at this overtemperature, chip temperature of the sensor and the ambient temperature (temperature measuring element in the second probe) is calculated and output the „true“ relative humidity.The sensor technology is optimally protected against contamination by a screwable sintered filter.As an option, a potential-free changeover contact and / or a backlit LCD display are available.The contents of the backlit display can be rotated by the menu in 90° increments. The actual value, the set switching threshold, the relay status, the MIN / MAX measured values of the selected interval, etc. can be read off.In addition, the switching threshold, hysteresis, offset value, etc. can be set directly on the device.
Measurement range temp.: | -20…+80°C |
Measurement range abs. humidity: | 0-20 g/m³, 0-25 g/m³ (calculated) selectable by DIP switch |
Measurement range wet bulb: | -30…+30°C, -20…+50°C (calculated) |
Measurement range air fuel ratio: | 0-20 g/kg, 0-25 g/kg (calculated) selectable by DIP switch |
Measurement range r.H.: | 0-100% r.H. |
Measurement range dew point: | -20…+50°C DP, 0…+50°C DP (calculated) selectable by DIP switch |
Accuracy humidity: | ±3% r.H. (30-70% r.H., else ±5% r.H., at 20°C) |
Accuracy temperature: | ±0,5 K |
Scales: | -20…+80°C, -0…+50°C, -50…+50°C, 0…+100°C selectable by DIP switch |
Temperature dependency: | ±0,02% r.H. / K (voltage output), ±0,04% r.H. / K (current version), ±0,05°C / 10 K (voltage version), ±0,07°C / 10 K (current output) |
Long term stability: | ±1%/year |
Sensor: | Combined electronic humidity and temperature sensor |
Sensor protection: | screwable stainless steel sintered filter, condensation protection by continuous heating approx. 3 K above ambient temperature |
Supply voltage: | 24 V AC/DC (±5%) |
Current consumption at 0-10 V: | typ. 50 mA |
Current consumption at 4-20 mA: | typ. 50 mA + max. 20 mA / output |
Analogue output 0-10 V: | 3-wire connection, load current < 0,1 mA, min. load resistance 100 kOhm |
Analogue output 4-20 mA: | 3-wire connection, max. RLoad(Ohm) = (+Ub – 15 V) / 0,02 A |
Alarm output: | 1 x potential-free change-over contact, 48 V, 1 A |
Switching Hysteresis Relay: | 2% of the selected scaling (without display), 0,5…5% of the selected scaling adjustable (with display) |
Electrical connection: | screw terminals max. 1,5 mm² |
Display: | optional LCD display with backlight on/off/auto |
Material: | Protection tube: stainless steel V2A |
Flow rate: | < 2 m/s |
Cable gland: | PG11 high-strength cable gland with strain relief |
Housing: | Polycarbonate PC UL 94 V0 with hinge locks, color signal white similar to RAL 9003 |
Dimensions: | Housing: L 89 x W 80 x H 47 mm, Protection tube: Ø 16 x 190 mm |
Protection type: | Housing/electronic: IP65, Sensor: IP30 |
Protection class: | III |
Working range r.H.: | 0…99% r.H., non-condensing air, slight pollutant concentration |
Working temperature: | -20…+70°C, -20…+50°C (Display) |
Storage temperature: | -20…+50°C |
Installation: | mounting flange (in scope of delivery) |
Approvals: | CE, EAC, RoHS |