- Resistance thermometer inputs, types Pt/Ni 100, Pt/Ni 500, Pt/Ni 1000
- Thermocouples inputs, types J, T, K, E, N, S, R, B, C or inputs a mV/T-characteristic curve. Selectable internal or external reference junction
- A bipolar mV-Voltage input. Free linearizing curves possible.
- Freely definable scaling of the quantity to be measured through stating range, decimal point position and unit from the list or defined unit.
- Zoom function, expanded scale, linearizing, inverse modus.
- Non-volatile saving of all set parameters.
- 4 measuring channels
The 4-channel transmitter AD-MV 554 GT is a programmable measuring device for measuring resistance and millivolt signals. Thanks to the integrated function blocks and free linearization curves, the AD-MV 554 GT can be used universally, preferably for temperature measurement with temperature sensors. The measured values are accessed via appropriate registers using the Modbus RTU protocol. Device addresses from 1 to 99 can be set using the address switches accessible on the front. All parameters are set up via the RS485 interface using the „AD-Studio“ PC configuration software. The interface parameters can also be set for inserting the devices into existing bus systems. The operating voltage is indicated by means of a green light-emitting diode. The data communication is signaled with a yellow light emitting diode. Invalid measuring signals outside the defined measuring range are detected. In this case the green LED flashes.
Resistance thermometer inputs Pt100, Pt500, Pt1000 to DIN EN 60751 | |
---|---|
Measuring range | -200 … +850 °C |
Connection method | 2-, 3-, 4-wire system |
Resolution | 16 Bit |
Accuracy | 2 K |
Smallest measuring spans | 30 K |
Max line resistance1) | 10 Ohm / cable |
Sensor supply | |
For 4-wire connection | < 500 µA |
For 2 – and 3-wire connection | < 250 µA |
1)With 2-conductor the line resistance comes as an offset into the measurement. | |
Resistance thermometer inputs Ni100, Ni500, Ni1000 to DIN EN 43760 | |
Measuring range | -60 … +230 °C |
Connection method | 2-, 3-, 4-wire system |
Resolution | 16 Bit |
Accuracy | 2 K |
Smallest measuring spans | 30 K |
Max line resistance1) | 10 Ohm / cable |
Sensor supply | |
For 4-wire connection | < 500 µA |
For 2 – and 3-wire connection | < 250 µA |
1)With 2-conductor the line resistance comes as an offset into the measurement. | |
Thermocouples | |
Comparative place: | |
Internal | Measurement at device terminals |
External | Cold junction temperatureselectable by parameters |
Resolution | 16 Bit |
Accuracy | 0,2 % of measuring range |
Measuring range type J | -200 … +1200 °C |
To DIN EN 60584: | |
Measuring range type T | -200 … +400 °C |
Measuring range type K | -200 … +1360 °C |
Measuring range type E | -200 … +1000 °C |
Measuring range type N | -200 … +1300 °C |
Measuring range type S | -40 … +1760 °C |
Measuring range type R | -40 … +1760 °C |
Measuring range type B | +400 … +1800 °C |
After standard ASTM E988: | |
Measuring range type C | 0 … +2320 °C |
Smallest measuring spans | 100 K |
Voltage inputs | |
Measuring range | -18 … +18 mV |
-36 … +36 mV | |
-72 … +72 mV | |
-144 … +144 mV | |
Resolution | 16 Bit |
Accuracy | 0,2 % of measuring range |
Transmission behaviour | |
Sampling rate | 1 measure / s |
Temperature influence | +/- 100 ppm / K of full scale |
RS485-Bus | |
Software protocol | Modbus-RTU |
Data format | 19200, e, 8, 1 |
Max. bus users | 99 |
Bus termination | 120 ohms both sides at the end |
Max. length of bus | 500 m (no spur lines) |
Cable | Twisted and shielded |
LEDs | |
Green [On] | Supply (blinking on error) |
Yellow [DATA] | RS485 Communication |
Controls | |
Address switch | 01 … 99 |
Supply | |
Supply voltage | 20 … 253 V DC / 50 … 253 V AC |
Max. power consumption | 0,6 W / 1,4 VA |
Housing | |
Dimensions (WxHxD) | 71 x 90 x 58 mm3 |
Manner of fastening | DIN rail mounting 35mm, EN 50022 |
Type of protection | IP 20 |
Connection method | Screw clamp |
Bolting torque terminals | 0,5 Nm |
Wire cross section | Max. 2,5 mm2 |
Weight | Ca. 30 g |
Environmental conditions | |
Permissible ambient temperature | -10 … +50 °C |
Storage and transport | -10 … +70 °C (no condensation) |
EMC | |
Product family standard2) | EN 61326-1 |
Emitted interference | EN 55011, CISPR11 Cl. B, Gr. 1 |
2)During electromagnetic disturbance minor changes in output signal are possible. | |
Electrical safety requirements | |
Product family standard | EN 61010-1 |
Overvoltage category | II |
Pollution degree | 2 |
Galvanic isolation, test voltages | |
Signal / supply unit | 3 kV, 50 Hz (1 min.) |
Signal / RS485 bus | Nogalvanic isolation |
Signal / Signal | Nogalvanic isolation |