The motion/brightness and temperature sensor BHT-D/A registers movement with an opening angle of 90°-110° over a scope of 360° with a coverage of approx. 10 m, the brightness from 0-1 kLux using a photo-diode and the temperature of the air in the environment from 0…50°C. The retention time of the motions sensor can be freely set between 5 seconds and 15 minutes using a 270° potentiometer. The unobtrusive housing with a clip fastening and reverse polarity protected socket is suitable for the quick assembly in intermediate ceilings. The motion sensor is used for motion dependent control processes, such as e.g. temperature or light control in offices.
Measuring principle: | alteration of position from persons and subjects with an temperature difference of > 3 K to the sensor |
Measurement range temp.: | 0…+50°C |
Measurement range motion: | motion yes/no, apex angle 90°/110° on 360° range, reach 10 m |
Measurement range brightness: | 0-1 kLux (0-0,5 kLux, 0-20 kLux, 0-50 kLux on request) |
Accuracy: | Lux: ±10% FS, Temp.: ±1 K |
Temperature dependency: | ±5% FS / 10 K |
Linearity inaccuracy: | < ±5% final value |
Sensor: | infrared motion sensor, photodiode, NTC10k |
Response time (t90): | Brightness/Motion: < 1 s, Temperature: < 60 s |
Sensor protection: | mounted inside housing |
Supply voltage: | 24 V AC/DC (±5%) |
Current consumption: | max. 40 mA at 24 V DC |
Analogue output 0-10 V: | 3-wire connection |
Alarm output: | 1 x potential-free change-over contact, 48 V, 1 A |
Threshold: | threshold for brightness-dependent motion detection adjustable by 270° potentiometer |
Offset: | ±10% from the selected measuring range by 270° potentiometer |
Electrical connection: | screw/plug terminals max. 1,5 mm² |
Running-in time: | < 3 s |
Holding time: | adjustable from 5 sec. up to 15 min. by 270° potentiometer |
Housing: | ABS polyman, colour signal white like RAL 9003 |
Dimensions: | Housing: Ø 80 mm, Cover: Ø 95 mm, Mounting depth: 50 mm |
Protection type: | IP20 |
Protection class: | III |
Working range r.H.: | 0…98% r.H. in contaminant-free, non-condensing air |
Working temperature: | 0…+50°C |
Storage temperature: | -20…+50°C |
Installation: | in the false ceiling by 2 tension springs |
Approvals: | CE, EAC, RoHS |