Produktdetails

Analog 1 1 isolation amplifier for standard current signals

Ursprünglicher Preis war: 123,05 €Aktueller Preis ist: 30,76 €.

SKU SK0121267-U Category Tag

24-Stunden-Versandgarantie

Bis zu 30 Tage für Rücksendungen

  • Supply buffer amplifier for 3-way separation of 0/4-20 mA signals (output follows input 1:1)
  • 18 mm narrow housing

  • The separation amplifier AD-TV 22 GL serves the galvanic separation and amplification of DC-current signals (0/4-20 mA). The output signal follows linear the input dimension and is independent of the connected burden up to a limiting value. Input, output and supply voltage are galvanically separate from each other with high insulation. An integral electronic power pack with a high degree of effectiveness prevents strong heating and allows high output loads. A high packing density is achieved in combination with a narrow type of construction.

    Application

    Burden amplification and galvanic decoupling of active DC-current signals in a cost-effective build-up.

    Input current
    Measuring range 0 … 20 mA; 4 … 20 mA
    Input resistance 50 Ohm
    Output current
    Output range 0 … 20 mA; 4 … 20 mA
    1:1 to the input signal
    Max. burden 400 Ohm
    Residual ripple <25 µAss
    Transmission behaviour
    Basic accuracy < 0,2 %
    Temperature influence < 100 ppm/K
    Supply
    Supply voltage 20 … 253 V DC / 50 … 253 V AC
    Nominal voltage 24 V DC / 230 V AC
    Power consumption 0,9 W / 2 VA
    Housing
    Dimensions (WxHxD) 18x81x103mm
    Type of protection IP 20
    Connection method Screw clamp
    Terminals, wire cross section 2,5 mm² flex wire / 4 mm² one wire
    Bolting torque terminals 0,5 Nm
    Manner of fastening DIN rail 35mm (EN 50022)
    Weight Ca. 100 g
    Environmental conditions
    Ambient temperature -10 … 50 °C
    Storage and transport -10 … 70 °C (no condensation)
    EMC
    Product family standard EN 61326-11)
    Emitted interference EN 55011, CISPR11 Cl. B, Gr. 1
    1)During electromagnetic disturbance minor changes in output signal are possible.
    Electrical safety requirements
    Product family standard EN 61010-1
    Overvoltage category II
    Pollution degree 2
    Functional safety
    Safety integrity level SIL 2 (IEC 61508)
    Galvanic isolation, test voltages
    Input/output 3,75 kV RMS (1 min.)
    Signal/auxiliary voltage 3 kV RMS (1 min.)
    Protective systems
    Input/output Electrical surge protection
    Power supply Electrical surge and reverse current protection