- Supply buffer amplifier for 3-way separation of 0/4-20 mA signals (output follows input 1:1)
- 18 mm narrow housing
The separation amplifier AD-TV 22 GL serves the galvanic separation and amplification of DC-current signals (0/4-20 mA). The output signal follows linear the input dimension and is independent of the connected burden up to a limiting value. Input, output and supply voltage are galvanically separate from each other with high insulation. An integral electronic power pack with a high degree of effectiveness prevents strong heating and allows high output loads. A high packing density is achieved in combination with a narrow type of construction.
Application
Burden amplification and galvanic decoupling of active DC-current signals in a cost-effective build-up.
Input current | |
---|---|
Measuring range | 0 … 20 mA; 4 … 20 mA |
Input resistance | 50 Ohm |
Output current | |
Output range | 0 … 20 mA; 4 … 20 mA |
1:1 to the input signal | |
Max. burden | 400 Ohm |
Residual ripple | <25 µAss |
Transmission behaviour | |
Basic accuracy | < 0,2 % |
Temperature influence | < 100 ppm/K |
Supply | |
Supply voltage | 20 … 253 V DC / 50 … 253 V AC |
Nominal voltage | 24 V DC / 230 V AC |
Power consumption | 0,9 W / 2 VA |
Housing | |
Dimensions (WxHxD) | 18x81x103mm |
Type of protection | IP 20 |
Connection method | Screw clamp |
Terminals, wire cross section | 2,5 mm² flex wire / 4 mm² one wire |
Bolting torque terminals | 0,5 Nm |
Manner of fastening | DIN rail 35mm (EN 50022) |
Weight | Ca. 100 g |
Environmental conditions | |
Ambient temperature | -10 … 50 °C |
Storage and transport | -10 … 70 °C (no condensation) |
EMC | |
Product family standard | EN 61326-11) |
Emitted interference | EN 55011, CISPR11 Cl. B, Gr. 1 |
1)During electromagnetic disturbance minor changes in output signal are possible. | |
Electrical safety requirements | |
Product family standard | EN 61010-1 |
Overvoltage category | II |
Pollution degree | 2 |
Functional safety | |
Safety integrity level | SIL 2 (IEC 61508) |
Galvanic isolation, test voltages | |
Input/output | 3,75 kV RMS (1 min.) |
Signal/auxiliary voltage | 3 kV RMS (1 min.) |
Protective systems | |
Input/output | Electrical surge protection |
Power supply | Electrical surge and reverse current protection |