Air Quality Transducer for CO for surface mounting, with display, with changeover contact, 0-10 V or 4-20 mA

Ursprünglicher Preis war: 339,28 €Aktueller Preis ist: 67,86 €.

SKU SK0120387-U Category Tag

24-Stunden-Versandgarantie

Bis zu 30 Tage für Rücksendungen

  • 0-200/500/1000 ppm
  • 0-10 V, 4-20 mA, changer
  • optional LCD-Display
  • hinge lock technology

  • The air quality sensor CO-A/A registers the CO concentration in the air in the environment in the range of 0-1000 ppm via an electro-chemical sensor and converts this measured value into a linear output signal 0-10 V respectively. 4-20 mA.As an option the air quality sensor has a potential-free changeover contact and a backlit display. The display content can be rotated in 90° steps using a menu and the measured value, the switching threshold set, the state of the relay, the MIN/MAX measured values for the selected intervals (1 h / 6 h / 12 h / 24 h) etc. can be read out.3 different measuring ranges can be selected 0-200 ppm, 0-500 ppm, 0-1000 ppm which can be switched, according to requirements, by the innovative DIP switching technology.

    Measurement range CO: 0-1000 ppm
    Scales: 0-200/500/1000 ppm
    Accuracy: ±5 ppm + max. ±5% f. mv (at 20°C, 50% r.H.)
    Temperature dependency: CO: ±2 ppm / K
    Long term stability: ±1% FS/year
    Sensor: Electrochemical sensor
    Response time (t90): < 5 min
    Sensor protection: sinter filter
    Supply voltage: 24 V AC/DC (±5%)
    Current consumption: max. 100 mA
    Analogue output 0-10 V: 3-wire connection
    Analogue output 4-20 mA: 3-wire connection
    Alarm output: 1 x potential-free change-over contact, 48 V, 1 A
    Switching Hysteresis Relay: 2% FS (without Display), 0,5…5% FS adjustable (with Display)
    Electrical connection: screw terminals max. 1,5 mm²
    Display: optional LCD display with backlight on/off/auto
    Running-in time: 1 min
    Initial operation: After switch-on of the device it runs a self-test and the zero-point calibration. This process takes, depending on ambient conditions, about 1 minutes. Within this time, the linear output signal deviates from the actual measured value.
    Cable gland: PG11 high-strength cable gland with strain relief
    Housing: Polycarbonate PC UL 94 V0 with hinge locks, color signal white similar to RAL 9003
    Dimensions: Housing: L 89 x W 80 x H 47 mm
    Protection type: Housing/electronic: IP65, Sensor: IP30
    Protection class: III
    Working range r.H.: 0…98% r.H. in contaminant-free, non-condensing air
    Working temperature: 0…+50°C
    Storage temperature: -20…+50°C
    Installation: screw fastening
    Approvals: CE, EAC, RoHS