  • Resistance thermometer inputs, types Pt/Ni 100, Pt/Ni 500, Pt/Ni 1000
  • Thermocouples inputs, types J, T, K, E, N, S, R, B, C or inputs a mV/T-characteristic curve. Selectable internal or external reference junction
  • A bipolar mV-Voltage input. Free linearizing curves possible.
  • Freely definable scaling of the quantity to be measured through stating range, decimal point position and unit from the list or defined unit.
  • Zoom function, expanded scale, linearizing, inverse modus.
  • Non-volatile saving of all set parameters.
  • 4 measuring channels

  • The 4-channel transmitter AD-MV 554 GT is a programmable measuring device for measuring resistance and millivolt signals. Thanks to the integrated function blocks and free linearization curves, the AD-MV 554 GT can be used universally, preferably for temperature measurement with temperature sensors. The measured values are accessed via appropriate registers using the Modbus RTU protocol. Device addresses from 1 to 99 can be set using the address switches accessible on the front. All parameters are set up via the RS485 interface using the „AD-Studio“ PC configuration software. The interface parameters can also be set for inserting the devices into existing bus systems. The operating voltage is indicated by means of a green light-emitting diode. The data communication is signaled with a yellow light emitting diode. Invalid measuring signals outside the defined measuring range are detected. In this case the green LED flashes.

    Resistance thermometer inputs Pt100, Pt500, Pt1000 to DIN EN 60751
    Measuring range -200 … +850 °C
    Connection method 2-, 3-, 4-wire system
    Resolution 16 Bit
    Accuracy 2 K
    Smallest measuring spans 30 K
    Max line resistance1) 10 Ohm / cable
    Sensor supply
    For 4-wire connection < 500 µA
    For 2 – and 3-wire connection < 250 µA
    1)With 2-conductor the line resistance comes as an offset into the measurement.
    Resistance thermometer inputs Ni100, Ni500, Ni1000 to DIN EN 43760
    Measuring range -60 … +230 °C
    Connection method 2-, 3-, 4-wire system
    Resolution 16 Bit
    Accuracy 2 K
    Smallest measuring spans 30 K
    Max line resistance1) 10 Ohm / cable
    Sensor supply
    For 4-wire connection < 500 µA
    For 2 – and 3-wire connection < 250 µA
    1)With 2-conductor the line resistance comes as an offset into the measurement.
    Thermocouples
    Comparative place:
    Internal Measurement at device terminals
    External Cold junction temperatureselectable by parameters
    Resolution 16 Bit
    Accuracy 0,2 % of measuring range
    Measuring range type J -200 … +1200 °C
    To DIN EN 60584:
    Measuring range type T -200 … +400 °C
    Measuring range type K -200 … +1360 °C
    Measuring range type E -200 … +1000 °C
    Measuring range type N -200 … +1300 °C
    Measuring range type S -40 … +1760 °C
    Measuring range type R -40 … +1760 °C
    Measuring range type B +400 … +1800 °C
    After standard ASTM E988:
    Measuring range type C 0 … +2320 °C
    Smallest measuring spans 100 K
    Voltage inputs
    Measuring range -18 … +18 mV
    -36 … +36 mV
    -72 … +72 mV
    -144 … +144 mV
    Resolution 16 Bit
    Accuracy 0,2 % of measuring range
    Transmission behaviour
    Sampling rate 1 measure / s
    Temperature influence +/- 100 ppm / K of full scale
    RS485-Bus
    Software protocol Modbus-RTU
    Data format 19200, e, 8, 1
    Max. bus users 99
    Bus termination 120 ohms both sides at the end
    Max. length of bus 500 m (no spur lines)
    Cable Twisted and shielded
    LEDs
    Green [On] Supply (blinking on error)
    Yellow [DATA] RS485 Communication
    Controls
    Address switch 01 … 99
    Supply
    Supply voltage 20 … 253 V DC / 50 … 253 V AC
    Max. power consumption 0,6 W / 1,4 VA
    Housing
    Dimensions (WxHxD) 71 x 90 x 58 mm3
    Manner of fastening DIN rail mounting 35mm, EN 50022
    Type of protection IP 20
    Connection method Screw clamp
    Bolting torque terminals 0,5 Nm
    Wire cross section Max. 2,5 mm2
    Weight Ca. 30 g
    Environmental conditions
    Permissible ambient temperature -10 … +50 °C
    Storage and transport -10 … +70 °C (no condensation)
    EMC
    Product family standard2) EN 61326-1
    Emitted interference EN 55011, CISPR11 Cl. B, Gr. 1
    2)During electromagnetic disturbance minor changes in output signal are possible.
    Electrical safety requirements
    Product family standard EN 61010-1
    Overvoltage category II
    Pollution degree 2
    Galvanic isolation, test voltages
    Signal / supply unit 3 kV, 50 Hz (1 min.)
    Signal / RS485 bus Nogalvanic isolation
    Signal / Signal Nogalvanic isolation