Air Quality Transducer for CO2, temperature for surface mounting, temperature probe led out, with display, with changeover contact, 2 x 0-10 V

Ursprünglicher Preis war: 448,73 €Aktueller Preis ist: 89,75 €.

SKU SK0120359-U Category Tag

24-Stunden-Versandgarantie

Bis zu 30 Tage für Rücksendungen

  • 0-2000/5000/10000 ppm
  • 0…+50°C
  • non-dispersive infrared sensor (NDIR)
  • 0-10 V, changer
  • hinge lock technology

  • The air quality sensor CO2T-A/A registers the CO2 concentration in the air in the environment in the range of 0-10000 ppm via a nondispersive infrared sensor (NDIR) and the air temperature 0…+50°C. The measuring transducer converts this measured value into a linear output signal 0-10 V.As an option the air quality sensor has a potential-free changeover contact and a backlit display. The changeover contact can be defined for one of the two measured values. The display content can be rotated in 90° steps using a menu and the measured value, the switching threshold set, the state of the relay, the MIN/MAX measured values for the selected intervals (1 h / 6 h / 12 h / 24 h) etc. can be read out.3 different measuring ranges can be selected (0-2000 ppm, 0-5000 ppm, 0-10000 ppm) which can be switched, according to requirements, by the innovative DIP switching technology.The zero point balance depending on the actual ambient conditions can be performed on the device by manual calibration. The quality sensor performs an automatic self-calibration at regular interval, thus ensuring a long-term stable CO2 measurement.

    Measurement range temp.: 0…+50°C
    Measurement range CO2: 0-10000 ppm, scales: 0-2000/5000/10000 ppm
    Scales: 0-2000/5000/10000 ppm
    Accuracy: 0-2000 ppm: ±50 ppm + 2% f. mv, 0-5000 ppm: ±50 ppm + 3% f. mv, else: ±100 ppm + 5% f. mv (at 20°C, 1013 mbar, auto-calibration ON), ±1 K
    Temperature dependency: CO2: ±5 ppm / K
    Long term stability: ±1% FS/year
    Sensor: CO2: non-dispersive infrared sensor (NDIR); Temperature: resistance sensor
    Response time (t90): < 5 min
    Sensor protection: sinter filter
    Supply voltage: 24 V AC/DC (±5%)
    Current consumption: Ø 100 mA
    Analogue output 0-10 V: 3-wire connection
    Alarm output: 1 x potential-free change-over contact, 48 V, 1 A
    Switching Hysteresis Relay: 2% FS (without Display), 0,5…5% FS adjustable (with Display)
    Electrical connection: screw terminals max. 1,5 mm²
    Display: optional LCD display with backlight on/off/auto
    Automatic calibration: The automatic CO2 calibration takes place every 7 days, this compensates for any drifts and achieves excellent long-term stability. To ensure this function, the device must be supplied with power for at least 7 days without interruption and ventilated once with fresh air (CO2 300…400 ppm) for approx. 10 minutes within this period.For the CO2 calibration, the device saves the minimum CO2 value measured during this period internally. After 7 days, this minimum value is normalized to 400 ppm CO2 and the output signal corrected accordingly. The maximum correction is limited to half of the determined drift. If the measured value falls below approx. 300 ppm, the calibration is initialized to 400 ppm.The automatic calibration can be deactivated if necessary and performed manually.
    Pressure dependency: CO2: 0,16% f. mv/hPa
    Running-in time: 10 min
    Initial operation: After switch-on of the device follows a self-test and the tempering, which takes ca. 10 minutes depending on the environmental conditions. At this time the analogue output drifts from the actual measurement value.
    Cable gland: PG11 high-strength cable gland with strain relief
    Housing: Polycarbonate PC UL 94 V0 with hinge locks, color signal white similar to RAL 9003
    Dimensions: Housing: L 89 x W 80 x H 47 mm
    Protection type: Housing/electronic: IP65, Sensor: IP30
    Protection class: III
    Working range r.H.: 0…98% r.H. in contaminant-free, non-condensing air
    Working temperature: 0…+50°C
    Manual calibration: The manual CO2 calibration of the output signal to 400 ppm (zero point) is started by pressing the button on the circuit board (hold it down for approx. 5 seconds until the LED flashes). Before that, continuous operation of min. 10 minutes in fresh air. The LED is deactivated after successful calibration.
    Storage temperature: -20…+50°C
    Installation: screw fastening
    Approvals: CE, EAC, RoHS